Features:
High efficiency£¨89%£©£¬low dissipation
Built-in passive PFC function compliance to EN61000-3-2
Protections: Short circuit/ Over load/ Over voltage/ Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
LED indicator for power on
100% full load burn-in test
EN61000-6-2(EN50082-2) industrial immunity level
3 years warranty
Dimensions: 227*125.2*100mm (W*H*D)
Model
DR-480-24
DR-480-48
DC Voltage
24V
48V
Voltage Tolerance
¡À1%
¡À1%
Rated Current
20A
10A
Current Range
0-20A
0-10A
Rated Power
480W
480W
Ripple & Noise
120mVp-p
120mVp-p
DC Adjustment Range
24-48V
48-53V
Setup, Rise Time
1200ms,40ms/230VAC at full load
Hold Time
16ms/230VAC
INPUT
Voltage Range 180~264VAC47¡«63 Hz£»250¡«370VDC
AC Current 4A/ 230 V
Efficiency 89%
Inrush Current Cold start40A/230V
Leakage Current £¼3.5mA/240VAC
PROTECTION
Over Load 105%¡«150%
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over Voltage 30-36V( HDR-480-24);54-60V(HDR-480-48)
Protection type: Shut down o/p voltage, re-power on to recover
OVER TEMP. 100¡æ¡À5¡æ(TSW)
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down
ENVIRONMENT
Working Temp., Humidity -20¡æ¡«+70¡æ£»20%¡«90 %RH
Storage Temp., Humidity -20¡æ¡«+85¡æ£»10%¡«95 %RH
Vibration 10¡«500Hz£¬2G 10min./1cycle, period for 60min, each along X, Y, Z axes
SAFETY
Withstand Voltage I/P-O/P: 3KVACI/P-FG: 1.5KVACO/P-FG: 0.5KVAC
Isolation Resistance I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC
STANDARD
Safety Standard Design refer to UL508,UL60950-1£¬TUV EN60950-1
EMC Standard EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2(EN50082-2)
OTHERS
Weight 2.4Kg
Packing 6pcs/15Kg/1.75CUFT
NOTE 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25¡æ of ambient temperature.
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12¡åtwisted pair-wire terminated with a 0.1¦Ì & 47¦Ìparallel capacitor.
3.Tolerance: includes set up tolerance, line regulation and load regulation.