Electrical Items >> Surge Arrester >> BY2 Surge Arrestor ¡¡

BY2 Surge protective device (Surge Arrestor)

BY2-30/2.5 BY2-60/2.5 BY2-60/4.0
Specificaton
Type

Uc (v)

Peak (kV)

Q (As)

Up (kV)

Ip(kA)

BY2-30/2.5 385 30 15 <2.5 4.5
BY2-30/4.0 385 30 15 <4.0 4.5
BY2-60/2.5 385 60 30 <2.5 6.0
BY2-60/4.0 385 60 30 <4.0 6.0
Usage and the Scope of Application
BY2 type SPD is suiting to A.C 50/60 Hz , 380V and the following electric power systems, such as TT , IT ,TN-S , TN-C and TN-C-S . The product functions as equi-potential connection in case of lightning striking at the joint of LPZOA and LPZ1 or LPZOS and LPZ1. It protects the electric network shocked by the thunder or surge over voltage and it also can be used in the TT system when combined with the voltage limiting SPD formed as the " 3+1 "type.
Technical Parameters
BY2-30/2.5 BY2-30/4.0 BY2-60/2.5 BY2-60/4.0
Maximum continuous operating voltage Uc 385V AC 385V AC 385V AC 385V AC
Power frequency arcing voltage Uf > 1.0kV > 1.5kV > 1.0kV > 1.5kV
Test grade Class ? Class ? Class ? Class ?
Insulating resistance (Risol) > 5 M O > 5 M O > 5 M O > 5 M O
Voltage protective level Up < 2.5 kV < 4.0 kV < 2.5 kV < 4.0 kV
Response time ns < 100 ns < 100 ns < 100 ns < 100 ns

Impulse peak current

30 kA 30 kA 60 kA 60 kA
Electric charge Q 15As 15As 30As 30As
Nominal discharge current In(8/20 µ s) kA 100 kA 100 kA 200 kA 200 kA
Rated disconnection follow current £¦#118alue Ip 4.5kA/250V 4.5kA/250V 6.0kA/250V 6.0kA/250V
The rated current of fuse 125A 125A 250A 250A
Defending grade IP20 IP20 IP20 IP20
Main Structure and Operating Principle
In figure 6, the electrodes are connected to the L /N line and PE line responsively , between the electrodes there will produce the electric interval . In normal situation , the protective device is high resistance , when the over voltage brings for electric network shocked by thunder or other reasons , the protective device will rapidly conduct and release the energy by arc light .As the impulse wave through it and after disappear, the protective device will recover to high resistance and not influence the normal operating .
Appearance and Installation Dimension
Installation Location and Application
SPD Class 1 ,functioning as an equi-potential connection in case of lightning.

Installed at the joint of the LPZOA, LPZOB and LPZ1 zones.

It is usually installed in low voltage main distribution cabinet connected to the incoming end of the buildings.

It adopts 35 mm DIN rail and is linked by 2.5 -- 35 mm² copper wire, the earth cable should choose the double color wire which is over 4 mm².