Multifunctional Magnetic Hydraulic Circuit breakerBreaker for Equipment L-MN5-50 Series

 

Range of use:

  L-MN5-50 is a new generation of minitype breakers to international standard and with superior structure. Functioned as protection to overload and short circuit for electrical system below 50HZ230V, 415V* or 400HZ, 280V*, or for the unfrequent connecting and breaking, they are widely used in the control system of computers, peripheral equipments, precision arc welders, communication equipments, power system, UPS equipments, railroad locomotives, ships, elevators and so on, as well as in petrol generator sets.
  This type of breakers (CBE) for equipment conform to GB177011999 and EN 609342001, and have been certified to TUV, CCC and CE.
  They can be equipped with auxiliary contacts, shunt releases and etc. for signal indication and distant operation, making your design or equipment functions greatly upgraded, and range of use more extensive, while the total cost can be lowered.

Model and meaning:
working conditions:

1. Ambient air temperature -40°C~+85°C
2. Relative humidity of air not greater than 95% (+40°C)
3. Gradient to vertical surface not exceeding 5 degrees.
4. Occasion with impact and vibration.
5. No gas and dust (including conductive dust) in non-explosive medium that can corrode the metal or damage the insulation.
6. Area not to be invaded by rain or snow.

Overall and installation dimensions:
                           
Curve2
50/60Hz
 
In.%
125
150
200
300
400
500
600
maximum &#118alue
175
60
20.0
5.00
2.30
1.50
.75
minimum &#118alue
10
6
2.5
.75
.30
.17
.055
time of delay
             
Curve3
50/60Hz
 
In.%
125
150
200
300
400
500
600
maximum &#118alue
17
4.50
1.60
.46
.250
.18
130
minimum &#118alue
1
.40
.16
.06
.035
.02
.009
time of delay
             
In.%
125
150
200
300
400
500
600
maximum &#118alue
55.0
20.0
7.50
2.80
1.40
800
.480
minimum &#118alue
2.1
1.2
.60
.27
.15
.085
.029
time of delay
             
In.%
125
150
200
300
400
500
600
最大值
7.0
3.50
1.40
.420
.250
.180
.120
最小值
.6
.35
.15
.055
.035
.021
.012
中延时
             
Multifunctional Hydraulic-electromagnetic Breaker for Equipment L-MN5-50 Series
Model L—MN5—50
Standard Gb17701—1999 En60934:2001
rated current 1—30A
rated short-circuit connecting and breaking capacity AC50HZ230V1000A0—C0—C0
insulation resistance 500V, 100M (Cooled down)
industrial frequency withstand voltage 50HZ.2500V.60S
life span Mechanical life 10,000 times
ambient temperature -40℃—±85℃
Low air pressure 5.8510Pa(439mm)
vibration resistance Frequency: 1055Hz1.5mm
impact resistance Impact resistance speed 50g, pulse width11ms, impulse wave: times of semi-positive shocks 3 times from 18 directions, shock direction: X.Y.Z.Z direct and reverse 6 directions.
rated working voltage DC65V,AC230V
pole number 13 (Pole)
type of connection Bolt type, screw lever type, fork type, bolt type, screw lever type, fork type
25±2℃running time belt
type of power supply
1In
1.25In
1.5In
4In
6In
A
Non-operative
10-120
6-60
0.2-3
0.02-2
B
Non-operative
2-60
1.8-30
0.15-2
0.04-1